Description
- Working voltage: 9V~24V
- Input: J-type thermocouple
- Output voltage: 0.00V~5.00V/0.00V~10.00V
- Temperature measurement range: - 100~+1000 (degrees)
- Dimensions: (length) 26mm * (width) 23mm * (height) 10mm
Module Parameters
1. Working voltage: 9V~24V
2. Input: J-type thermocouple
3. Output voltage: 0.00V~5.00V/0.00V~10.00V
4. Temperature measurement range: - 100~+1000 (degrees).
5. Output mode: J1 pad on the circuit board: open circuit (output 0.00V~5.00V); Short circuit (output 0.00V~10.00V), default is open circuit. 6. Application scope: remote data acquisition and control equipment;
7. Dimensions: (length) 26mm * (width) 23mm * (height) 10mm
8. Module interface:
24V: Power supply positive electrode interface (9V~24V).
G: Power ground interface.
I+: thermocouple positive electrode interface.
I -: thermocouple negative electrode interface.
OUT: signal output interface (0.00V~5.00V/0.00V~10.00V).
G: Power ground interface.
Note: When outputting 0.00V to 10.00V, the power supply voltage should be 15V.
Output (0.00V~5.00V) resolution: 0.00454545V/ (V/)
Output (0.00V~10.00V) resolution: 0.00909090V/ (V/)
The formula for calculating the measured temperature: (output voltage (V)/resolution) - 100 =measured temperature ().
Package1pc Thermocouple to Voltage J-type to 0-5V 0-10V Linear Conversion Transmitter Module